APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21887 Issued:2013-03-07
Revised:New
Style 21887 Multiple-conductor cable using non-integral jacket.

Rating105 deg C, 600 V ac, Cable flame.
Insulated ConductorLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more insulated conductors, twisted pairs, groups of twisted conductors or singles or groups of singles laid parallel to form flat, oval or round cable. A barrier layer and/or fillers are optional.
ShieldOptional.
CoveringOptional.
JacketExtruded PVC.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024