APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21896 Issued:2013-04-08
Revised:New
Style 21896 Multiple-conductor cable with extruded non-integral jacket.

Rating105 deg C,600 Vac, Cable flame; Oil Res 60 deg C(required); Sunlight Res (required).
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC - See Facing Page for compound.
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less60 mils48 mils
0.701-1.500 inch80 mils64 mils
1.501-2.500 inch110 mils88 mils
2.501 inch and larger140 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.