APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21897 Issued:2013-04-19
Revised:New
Style 21897 Multiconductor Cable with Extruded Non-Integral Jacket

Rating80 deg C, no voltage specified, Cable flame.
Conductor36 AWG Min., solid or stranded.
InsulationLabeled or Complies with manufacturer's AWM Procedure, and having a Singles min rating of 80 deg. C. The designations of all styles of individual cables used in making up the cable assembly shall be available.
JacketPolyurethane(PUR). One layer or two layers jacket, thickness in accordance with below. Two layers jacket are extruded simultaneously and not separable in the same base compound, but should be differed with colour. A textile braid placed between two layers jacket. The thickness of individual layer is not specified. One layer jacket Thickness (mils) or two layers total thickness (mils). Diameter of cable under jacket, Minimum average thickness, Minimum thickness at any point; 0.425 inch or less, 45 mils, 36 mils; 0.426 - 0.700 inch, 60 mils, 48 mils; 0.701 - 1.500 inch, 80 mils, 64 mils; 1.501 - 2.500 inch, 110 mils, 88 mils; 2.501 inch and larger, 140 mils, 112 mils.
CoveringOptional - 4 mil or heavier wall of PVC or other thermoplastic covering may be extruded over the conductor assembly or groups of conductors (with or without shields).
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseAs external interconnection of electronic equipment (such as computers and business machines).

UL and the UL Logo are trademarks of UL LLC © 2024