APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21921 Issued:2013-08-13
Revised:2013-08-21
Style 21921 Multiple-conductor cable using non-integral jacket.

Rating85 deg C,100 Vac Cable flame; Sunlight Res (optional).
Conductor30 AWG - 4/0 AWG, solid or stranded.
InsulationExtruded FRPE, 14 mils minimum average thickness, 12 mils minimum thickness at any point
CoveringOptional
ShieldOptional
AssemblyTwo or more insulated singles twisted together. Lay not specified. Fillers, Shields, Braids and/or barrier layers description of each assembly.
JacketExtruded FRPE.
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.400 inch or less24 mils20 mils
0.401-0.700 inch30 mils24 mils
0.701-1.500 inch45 mils36 mils
1.501-2.500 inch60 mils48 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring and External Wiring

UL and the UL Logo are trademarks of UL LLC © 2024