Rating | 80 deg C, 1000 Vac, Cable flame. |
|
Insulation | Labeled Style 11538. |
|
Assembly | Consists of two or more conductors, twisted pairs, or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. M ay use same or mixed AWG size. |
|
Separator | Optional. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded TPU |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 35 mils | 28 mils |
| 0.701 - 1.000 inch | 60 mils | 48 mils |
| 1.001 - 1.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|