Rating | 125 deg C, 1000 Vac, Cable flame. |
|
Conductor | 50 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. May use same or mixed AWG size. |
|
Shield | Optional |
|
Covering | Optional |
|
Jacket | Extruded TPE |
| Diameter under the jacket in inches | min average | minimum at any point |
| 0.700 or less | 30 mils | 24 mils |
| 0.701-1.000 dia | 45 mils | 36 mils |
| 1.001-1.500 dia | 60 mils | 48 mils |
| 1.501-2.500 dia | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring. |
|