APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21972 Issued:2015-02-09
Revised:2015-02-26
Style 21972 Multiple-conductor Cable using non-integral jacket

Rating105 deg C, -40 deg C, 300 Vac, Horizontal Flame Test, Cable Flame Test, 60 deg C wet (required); Sunlight Res (required).
InsulationExtruded PVC, 30 mils minimum average thickness, 27 mils minimum thickness at any point. Any Recognized Component (QMTT2) PVC Compound acceptable for use on Types TW, THW, THW-2 and THHW.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly.
JacketExtruded PVC, Any Recognized Component (QMTT2) 720 hours sunlight Resistance PVC Compound.
Diameter of core assembly under jacketMinimum average thickness (mils)Minimum thickness at any point (mils)
0 - 0.7003024
0.701 - 1.0004536
1.001 - 1.5006548
1.501 - 2.5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Use Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024