APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21986 Issued:2015-03-27
Revised:New
Style 21986 Multi-conductor cable with extruded non-integral jacket.

Rating105 deg C, 1000 Vac; Cable flame; -60 deg C (optional); ,Oil Res 60 (optional); Sunlight Res (optional); Ozone Res (Optional).
Conductor50 AWG - 10 AWG, solid or stranded.
InsulationLabeled or complying with manufacturer's Procedure.
AssemblyTwo or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional.
JacketTPU
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.000 inch110 mils88 mils
4.001 inch and larger140 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024