APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22001 Issued:2015-05-18
Revised:New
Style 22001 Multi-Conductor cable with extruded non-integral jacket

Rating80 deg C, 9000 Vdc, Cable flame.
Conductor32 AWG - 10 AWG, solid or stranded.
InsulationExtruded XLPE, 45 mils minimum average thickness, 41 mils minimum thickness at any point.
AssemblyTwo or more singles or groups of twisted singles twisted together. Lay not specified. Barrier layers, tape(s) and/or fillers optional.
ShieldOptional - metal tape(s) and/or metal braid(s).
CoveringOptional.
JacketExtruded PVC
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
1.500 inches or less68 mils54 mils
1.501 -2.500 inches80 mils64 mils
2.501-4.500 inches110 mils88 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024