APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22015 Issued:2015-09-10
Revised:2015-09-11
Style 22015 Parallel Cable Using Extruded Non-Integral Jacket

Rating90 deg C,600 Vac, Cable flame.
ConductorType TFFN, 18 AWG - 16 AWG solid or stranded round. Type THHN, 14 AWG to 10 AWG - copper and 12 AWG to 10 AWG - aluminum or copper-clad aluminum. Type THHN, 14 AWG to 10 AWG - copper and 12 AWG to 10 AWG aluminum or copper-clad aluminum. Type TFFN, 18 AWG - 16 AWG solid or stranded round. Type THHN, 14 AWG to 10 AWG - copper and 12 AWG to 10 AWG aluminum or copper-clad aluminum.
InsulationUL Listed Type THHN or TFFN.
AssemblyTwo conductors, Type THHN and/or TFFN, laid flat with a shield (optional), drain wire (optional) and overall jacket.
ShieldOptional, two wire serves, one wrapped around each insulated conductor.
JacketExtruded PVC, 20 mils minimum average thickness, 16 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Wiring.