APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22022 Issued:2015-12-03
Revised:New
Style 22022 Multi-conductor cable with non-integral jacket

Rating90 deg C, 1000 Vac, Horizontal flame.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketTPE
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inces or less30 mils24 mils
0.701-1.000 in45 mils36 mils
1.001-1.500 in60 mils48 mils
1.501-2.500 in80 mils64 mils
2.501-4.000 in110 mils88 mils
4.001 in or larger140 mils112 mils
*Major dia if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024