Rating | 80 deg C, 300 Vac, Cable flame. |
|
Insulation | Labeled or complying with the manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs or groups of twisted singles twisted together; or singles or groups of singles, may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | A metal shield(s) shall be provided. |
|
Covering | Optional. |
|
Jacket | Extruded TPE. |
| Diameter of cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.300 inch or less | 68 mils | 54 mils |
| 0.301-0.700 inch | 78 mils | 62 mils |
| 0.701-1.000 inch | 90 mils | 72 mils |
| 1.001-1.500 inch | 105 mils | 84 mils |
| 1.501-2.500 inch | 120 mils | 96 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|