APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22049 Issued:2016-07-14
Revised:New
Style 22049 Multiple-Conductor Cable Using Non-Integral Jacket

Rating90 deg C, 1000 Vac, Cable Flame.
Conductor40 AWG minimum
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more conductors or groups of conductors laid parallel or twisted forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. May use same or mixed AWG size.
CoveringOptional, Extruded PVC, 6 mils minimum thickness at any point.
ShieldOptional.
JacketExtruded PVC
Diameter of Cable under jacket in inches*minimum avg. thickness in milsminimum thickness at any point in mils
0.700 or less3024
0.701 - 1.0006048
1.001 - 1.5018064
1.501 - 2.50011088
* - Major diameter if cable is flat or oval
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring or Internal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024