APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22066 Issued:2016-11-09
Revised:2016-11-15
Style 22066 Multiple conductor cable with extruded non-integral jacket

Rating80 deg C, 300 Vac, VW-1 flame.
InsulationLabeled or complying with the manufacturer's AWM file.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductor is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional.
JacketExtruded TPU
Diameter of cable under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0 - 0.7003024
0.701-1.0004536
1.001-1.5006048
1.501-2.5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial - External Wiring with VW-1 Flame Rating only.

UL and the UL Logo are trademarks of UL LLC © 2024