APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22074 Issued:2017-01-11
Revised:2017-01-20
Style 22074 Multiple-conductor cable using non-integral jacket

Rating105 deg C, 1000 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's Procedure.
AssemblyTwo (2) or more conductors assembled in accordance with the Standard with optional fillers, binders, tapes, and shields.
ShieldOptional, metallic tape or metallic braid.
CoveringInner-Optional
JacketExtruded PVC
Diameter of core assembly under jacket(in.)Minimum average thickness (mils)Minimum thickness at any point (mils)
0 - 0.7003024
0.701 - 1.0004536
1.001 - 1.5006548
1.501 - 2.5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.