APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22079 Issued:2017-02-07
Revised:New
Style 22079 Multi-conductor cable with extruded non-integral jacket

Rating105 deg C, 300 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's Procedure.
AssemblyConsists of two or more singles, twisted pairs or groups of twisted singles twisted together. The singles or groups of singles may be laid parallel forming a flat, oval or round cable. The lay of the conductors are not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
Strength MemberOptional. A steel strength member insulated with the same grade and thickness of insulation as used on the circuit conductors, may be provided.
ShieldOptional.
CoveringOptional
JacketExtruded PVC.
Diameter of Core Assembly under Jacket@Minimum Average ThicknessMinimum Thickness at any point
0.700 inch or less30 mils24 mils
0.701 - 1.000 inch45 mils36 mils
1.001 - 1.500 inch60 mils48 mils
1.501 - 2.500 inch80 mils64 mils
@ - Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024