Rating | 300 deg C, 1000 Vac, Cable Flame on construction A, Horizontal flame on construction B. |
|
Insulation | Labeled or complying with AWM Procedure. 40 AWG minimum. |
|
Assembly | Consists of two or more conductors, twisted pairs, parallel pairs, or groups of twisted conductors or parallel pairs twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors are not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Jacket | Extruded ECA. |
| | Construction A | | Construction B | |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils | 10 mils | 8 mils |
| 0.701-1.000 inch | 45 mils | 36 mils | 10 mils | 8 mils |
| 1.001-1.500 inch | 60 mils | 48 mils | 10 mils | 8 mils |
| 1.501-2.500 inch | 80 mils | 64 mils | 10 mils | 8 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Construction A: Internal or external wiring. Construction B: Internal wiring only. |
|