APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22094 Issued:2017-06-19
Revised:New
Style 22094 Multiple-conductor cable using non-integral jacket

Rating60, 80, 90 or 105 deg C,-40 deg C; 300 or 600 Vac; Horizontal flame test or Cable flame test; Sunlight Res (required).
Conductor18 AWG - 2 AWG, solid or stranded.
InsulationExtruded PVC. 18-16 AWG conductor size 30 mils min average 27 mils minimum at any point 14-10 AWG 45 avg 40 min 8-2 AWG 60 avg 54 min
AssemblyConsists of three or more conductors. The conductors or groups of conductors may be laid parallel forming a flat or oval cable. May use same or mixed AWG size.
ShieldOptional.
JacketExtruded PVC, any Recognized Component (QMTT2) 720 hours sunlight Resistance PVC Compound. dia of cable under jacket is 0.700 inches or less* 60 mils min average 48 mils minimum at any point 0.701-1.000 in 80 avg 64 min 1.001-1.500 in 95 avg 76 min 1.501-2.500 in 110 avg 88 min *Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external wiring.