APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22095 Issued:2017-06-27
Revised:New
Style 22095 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating80 deg C, 30 Vac, Cable flame.
Insulated ConductorLabeled or complies with manufacturer's Procedure.
AssemblyTwo or more conductors, twisted pairs, or groups of twisted conductors. The conductors may be laid parallel or twisted together to form a flat, oval, or round cable construction. Each insulated conductor may be laid parallel and then 2 or more jackets may be co-extruded over each insulated conductor. Barrier layer, tapes and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional. Extruded PVC, 5 mils minimum thickness at any point, over the assembly or groups of singles.
ShieldOptional. May be over one or more of the insulated conductors or applied over the assembly.
JacketExtruded PVC. If parallel construction is rippable, the measurements are made after ripping.
Diameter of core assembly under jacket*Minimum average thicknessMinimum thickness at any point
0.250 inch or less20 mils16 mils
0.251-0.424 inch30 mils24 mils
0.425-0.700 inch60 mils48 mils
0.701-1.500 inch80 mils64 mils
1.501-2.500 inch110 mils88 mils
* = Major diameter if flat or oval construction.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring in Class 2 Circuits only.