Rating | 60 deg C, 350 Vdc / 300 Vac, Horizontal flame, Cable flame. VW-1 flame |
|
Conductor | Solid or stranded. |
|
Insulation | Extruded FEP, 4 mils minimum average thickness, 3 mils minimum at any point. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers/or Glass optical fiber optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket* | mils minimum average thickness | mils minimum thickness at any point |
| 0.425 inch or less | 30 | 24 |
| 0.426-0.700 inch | 45 | 36 |
| 0.701-1.000 inch | 60 | 48 |
| 1.001-1.500 inch | 80 | 64 |
| 1.501-2.500 inch | 110 | 88 |
| 2.501 inch and larger | 140 | 112 |
| * - Major diameter if cable is flat or oval. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection. |
|