APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22148 Issued:2018-02-23
Revised:2018-02-27
Style 22148 Multiple-conductor cable using non-integral jacket

Rating90 deg C, 300 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.000 inch110 mils88 mils
4.001 inch and larger140 mils112 mils
BraidOptional.
SeparatorOptional
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024