APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22190 Issued:2018-11-16
Revised:New
Style 22190 Multiconductor cable with Extruded Non-Integral Jacket

Rating105 deg C,-40 deg C,600 Vac; Horizontal flame; Cable flame; Moisture Res 60 (required); Sunlight Res (required).
Conductor24 AWG - 2 AWG, solid or stranded.
InsulationExtruded PVC. Any Recognized Component (QMTT2) PVC compound acceptable for use on Types TW, THW, THW-2 and THHW.
Conductor sizeMinimum average thicknessMinimum thickness at any point
24-10 AWG30 mils27 mils
9-8 AWG45 mils40 mils
7-6 AWG60 mils54 mils
5-2 AWG60 mils54 mils
AssemblyConsists of two or more more conductors. The conductors or groups of conductors may be laid parallel forming a flat or oval cable. May use same or mixed AWG size.
ShieldOptional.
JacketExtruded PVC. Any Recognized Component (QMTT2) 720 hours Sunlight Resistance PVC compound.
Diameter of core assembly under jacket*Minimum average thicknessMinimum thickness at any point
0-0.700 inch30 mils27 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch65 mils48 mils
1.501-2.500 inch80 mils64 mils
* = Major diameter if flat or oval construction.
StandardApplicance Wiring Material UL 758
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external wiring.