APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22191 Issued:2018-11-27
Revised:2019-11-07
Style 22191 Multiple-Conductor cable using non-integral extruded jacket

Rating105 deg C, 300 Vac, Cable Flame; Oil Res 60C or 80C (Optional), Moisture Resis 60C, 720hr Sunlight Resistance.
InsulationLabeled or complies with manufacturer's AWM Procedure having a minimum rating of 60 deg C wet.
AssemblyTwo or more twisted singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use mixed sizes of insulated singles.
ShieldOptional - may be over one or more of the insulated conductors or applied over the assembly.
JacketExtruded PVC. Recognized Component - Polymeric Materials for Use in Wire and Cable (QMTT2) 720 Hour Sunlight Resistant PVC Jacket Compounds or see Facing Page for compound
dia of cable under jacket
0.700 inches or less30 mils min average24mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024