APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22194 Issued:2018-12-03
Revised:2019-01-14
Style 22194 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating90 deg C, 600 Vac, Cable flame.
Conductor14 AWG - 1000 kcmil, solid or stranded.
InsulationTypes THHN, THWN, THWN-2 rated 90C dry, Types TFN or TFFN or equivalent labeled singles per Manufacturers AWM procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of conductors is not specified. A Drain Wire, barrier layer and/or fillers are optional. May use same or mixed AWG size. Types TFN and TFFN in 18-16 AWG only.
Coveringoptional
Shieldoptional
JacketExtruded PVC
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.700 or less3024
0.701-1.0006048
1.001-1.5008064
1.501-2.50011088
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.