Rating | 90 deg C, 600 Vac, Cable flame. |
|
Conductor | 14 AWG - 1000 kcmil, solid or stranded. |
|
Insulation | Types THHN, THWN, THWN-2 rated 90C dry, Types TFN or TFFN or equivalent labeled singles per Manufacturers AWM procedure. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of conductors is not specified. A Drain Wire, barrier layer and/or fillers are optional. May use same or mixed AWG size. Types TFN and TFFN in 18-16 AWG only. |
|
Covering | optional |
|
Shield | optional |
|
Jacket | Extruded PVC |
| Diameter of core assembly under jacket (inches) | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 60 | 48 |
| 1.001-1.500 | 80 | 64 |
| 1.501-2.500 | 110 | 88 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|