APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22210 Issued:2019-03-06
Revised:New
Style 22210 Flat Ribbon Cable with extruded Integral Insulation

Rating105 deg C, no voltage rating, Horizontal flame.
Conductor40 AWG - 10 AWG, solid or stranded.
InsulationExtruded ETFE, 5 mils minimum average thickness, 4 mils minimum thickness at any point.
AssemblyMultiple conductors laid parallel, Web thickness 2 mils minimum. The adjacent ground conductors within a row may touch.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial Use in protected areas in electronic equipment (such as data processing equipment and office appliances.)

UL and the UL Logo are trademarks of UL LLC © 2024