APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22225 Issued:2019-04-11
Revised:New
Style 22225 Multiple-conductor cable using non-integral jacket

Rating90 deg C, 300 Vac, Cable flame.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductor is not specified. A barrier layer, binders and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded TPU ;
Diameter of core assembly under jacketMinimum average thickness milsMinimum thickness at any point mils
0.700 inch or less3024
0.701-1.000 inch4536
1.001-1.500 inch6048
1.501-2.500 inch8064
2.501-4.500 inch11088
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.