APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22250 Issued:2019-05-31
Revised:2019-06-05
Style 22250 Multiple-Conductor Cable using Non-Integral Extruded Jacket

Rating105 deg C, 600 Vac, Horizontal flame; Optional - Oil Res 60C, 80C.
Conductor50 AWG - 10 AWG, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM procedure
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
JacketExtruded TPU, 30 mils min average, 24 mils minimum at any point.
ShieldOptional.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.