Rating | 90 deg C,1000 Vac Cable flame. |
|
Conductor | 26 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded PVC, 14 mils minimum average thickness, 12 mils minimum thickness at any point. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors into together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Jacket | Extruded PVC |
| Dia. of round at assembly under jacket* inches | Minimum average thickness mils | Minimum thickness at any point mils |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
| *Major diameter if flat or oval construction. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|