Rating | 90 deg C, 600 V, Cable flame. |
|
Insulated Conductor | Labeled or complying with manufacturer's AWM File. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. May be provided under or over covering, if provided. |
|
Covering | Optional. |
|
Jacket | Extruded TPU. |
| Diameter of cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 1.000 inch or less | 55 mils | 44 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|