Rating | 80 deg C, 600 Vac, Cable flame. |
|
Insulated Conductor | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. Two or more jacketed cables are laid parallel and bonded or heat bonded together with a web to form a flat cable. If the cable construction is rippable, measurements of jacket thickness shall be made after ripping. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701 - 1.000 inch | 45 mils | 36 mils |
| 1.001 - 1.500 inch | 60 mils | 48 mils |
| 1.501 - 2.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|