APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22292 Issued:2020-02-05
Revised:2020-03-06
Style 22292 Multiple-conductor cable using non-integral jacket.

Rating200 deg C, 600 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo insulated conductors laid parallel or two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A binder and/or fillers may be employed.
ShieldOptional
CoveringOptional
JacketExtruded FEP
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.250 inch or less8 mils6 mils
0.251-0.350 inch10 mils8 mils
0.351-0.500 inch13 mils10 mils
0.501-0.700 inch15 mils12 mils
0.701-1.500 inch20 mils16 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024