APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22342 Issued:2020-12-02
Revised:New
Style 22342 Multiple-Conductor Cable using Exruded Non-Integral Jacket.

Rating80 deg C, 600 Vac, Cable Flame.
Conductor50 AWG - 4 AWG, Solid or Stranded Round.
InsulationLabeled or complying with manufacturer's Procedure.
AssemblyTwo or more singles, twisted pairs of groups or twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional Inner Layer.
JacketExtruded TPU -
Dia of Cable under jacketmin averageminimum at any point
0.700 inch or less32 mils26 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024