APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22350 Issued:2021-03-17
Revised:New
Style 22350 Multiple-conductor cable using non-integral jacket

Rating90 deg C, 1000 Vac.
Conductor26 AWG min., solid or stranded.
InsulationLabeled or complying with the manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with not more than three rows of single conductors or groups of conductors. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
CoveringOptional. Extruded TPE or other thermoplastic, 4 mils minimum thickness at any point, may be extruded over the conductor assembly or groups of conductors (with or without shields).
ShieldOptional.
JacketExtruded TPE
Diameter of core assembly under jacket@Minimum average thicknessMinium thickness at any point
0.700 or less inch45 mils36 mils
0.701-1.000 inch60 mils48 mils
1.001-1.500 inch80 mils64 mils
1.501-2.500 inch110 mils88 mils
2.501 and larger140 mils112 mils
@- Major diameter if cable is flat or oval
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial. Internal Wiring or External Wiring without a flame rating.