Rating | 80 deg C,300 Vac Cable flame, VW-1 flame. |
|
Conductor | 50 AWG min. Solid or stranded. |
|
Insulation | Labeled. |
|
Assembly | Two or more twisted singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and or fillers optional. Two or three conductors and or conductor groups may be laid parallel to form flat cable. Manufacturer shall maintain a complete description of each assembly. Insulated conductor is built with optional shield over insulation, optional 1st covering, optional 2nd covering, optional shield over covering and optional 3rd covering. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Metallic Braid | Optional. |
|
Jacket | Extruded PVC |
| major dia. in inches |
| 0.700 or less | 30 mils min average | 24 mils minimum at any point |
| 0.701-1.000 dia | 45 avg | 36 min |
| 1.001-1.500 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
| 2.501-4.000 dia | 110 avg | 88 min |
| 4.001 dia and larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|