APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22374 Issued:2021-05-13
Revised:New
Style 22374 Multiple Conductor Cable using Non-Integral Extruded Jacket.

Rating90 deg C, 600 Vac, Cable Flame; Oil Res 60C (required); Moisture Res 75C (required).
Conductor40 AWG - 4/0 AWG, solid or stranded round.
InsulationLabeled or complying with Manufacturer's AWM Procedure. Shall employ insulation Style(s) rated for Mositure Res 75C.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch60 mils48 mils
1.001-1.500 inch80 mils64 mils
1.501-2.500 inch110 mils88 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring or Internal Wiring.