Rating | 90 deg C, 1000 Vac, Cable Flame |
|
Insulated Conductor | Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two or more singles or groups of twisted singles twisted together with overall metal braid and overall jacket. Lay not specified. Barrier layer and/or fillers optional. |
|
Shield | Required - Metallic Braid provided over the cable core. |
|
Jacket | Extruded PVC. |
| Diameter of cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|