APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22392 Issued:2021-09-22
Revised:New
Style 22392 Multiconductor Cable with Extruded Non-Integral Jacket

Rating80 deg C, 1000 Vac, Horizontal Flame.
Conductor36 AWG Min, Solid or Stranded.
InsulationLabeled or Complies with manufacturer's AWM Procedure, and having a Singles min rating of 80 deg. C, 1000 Vac.
AssemblyTwo or more singles or groups of twisted singles twisted together with optional covering, optional shield and overall jacket. Lay not specified. Barrier layer and/or fillers optional. The designations of all styles of individual cables used in making up the cable assembly shall be available. May use same or mixed AWG sizes.
CoveringOptional - 4 mil or heavier wall of PVC or other thermoplastic covering may be extruded over the conductor assembly or groups of conductors (with or without shields).
ShieldOptional.
JacketExtruded TPU. The jacket may be applied simultaneously in more than one color/layer provided that all layers are not separable and are of the same base compound (differ only in color). Jackets with a total thickness of 1.14 mm (0.045 in) and greater may have a reinforcement consisting of an open weave kevlar braid, placed between adjacent layers of the same base compound, that shall not be readily separable. The thickness of each individual layer is not specified.
Diameter of cable under jacket in inchesMinimum average thickness in milsMinimum thickness at any point in mils
0.425 or less4536
0.426 - 0.7006048
0.701 - 1.5008064
1.501 - 2.50011088
2.501 and larger140112
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.