Rating | 80 deg C, 600 Vac, Cable Flame. |
|
Conductor | 50 AWG - 4 AWG, solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups or twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Bare or Metal Coated Braid |
|
Covering | Optional inner layer. |
|
Jacket | Extruded TPU |
| Diameter of Cable under jacket in mils | mils min average | mils minimum at any point |
| 0.700 or less | 32 | 26 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|