APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22410 Issued:2021-12-22
Revised:2021-12-21
Style 22410 Multiple-conductor cable using non-integral jacket.

Rating80 deg C,60 V Cable flame.
Conductor44 AWG - 10 AWG, solid or stranded.
InsulationExtruded FEP, 2 mils minimum average thickness, 1 mils thickness at any point
AssemblyTwo or more conductors, twisted pairs, or groups of twisted conductors. The conductors may be laid parallel or twisted together to form a flat, oval, or round cable construction. Barrier layer, tapes and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
CoveringOptional.
JacketExtruded TPE.
Diameter of core assembly under jacketminimum average thicknessMinimum thickness at any point
1.500 inch or less13 mils10 mils
1.501-2.500 inch15 mils12 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring in Class 2 Circuits only.

UL and the UL Logo are trademarks of UL LLC © 2025