APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22433 Issued:2022-05-26
Revised:New
Style 22433 Multiple-conductor cable using non-integral jacket.

Rating80 deg C, 60 Vac, Cable flame.
Insulated ConductorLabeled or complying with Manufacture's AWM Procedure.
AssemblyTwo or more twisted singles or groups of twisted singles twisted together or groups may be laid parallel to form flat, oval, or round cables. Barrier layer and/or fillers optional. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded TPE.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
1.500 inch or less11 mils9 mils
1.501-2.500 inch15 mils12 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring in Class 2 circuits only.

UL and the UL Logo are trademarks of UL LLC © 2024