APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22438 Issued:2022-07-06
Revised:New
Style 22438 Multiple Conductor Cable with Extruded Non-integral Jacket.

Rating80 deg C, -30 deg C, 600 Vac, Horizontal Flame, 60 deg C Oil Res, Sunlight Res.
Conductor32 AWG minimum, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductor is not specified. A barrier layer and/or fillers are optional. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC, 15 mils minimum average thickness, 12 mils minimum thickness at any point. See Facing Page for Compound.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024