| Rating | 105 deg C,1000 Vac Cable flame. |
|
| Conductor | 30 AWG ~ 4/0 AWG, solid or stranded. |
|
| Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
| Assembly | Two or more singles, twisted pairs, groups of twisted singles or singles or groups of singles laid parallel to form a flat, oval or round cable. Core wrap tape, binder, fillers and/or sensor are optional. Sensor consists of 2C heat sensitive polymer layer extruded over each phosphor-bronze wire or tinned copper clad steel wire, with core wrap tape, FEP inner covering and PVC outer covering, and lay of sensor is not specified. Not evaluated as a sensor. |
|
| Jacket | Extruded PVC |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | External Wiring. |
|