Rating | 105 deg C,300 Vac; Cable Flame; VW-1 flame; Horizontal flame; Oil Res 60 (optional); Sunlight Res (optional). |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded PVC, For Sunlight Res Rating material shall be Any Recognized Component (QMTT2) 720 hours sunlight Resistance PVC Compound or see Facing page for compound. |
| Diameter of core assembly under jacket(inch) | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 0 - 0.700 | 30 | 24 |
| 0.701 - 1.000 | 45 | 36 |
| 1.001 - 1.500 | 65 | 48 |
| 1.501 - 2.500 | 80 | 64 |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring. |
|