Rating | 80 deg C, 300 Vac, FT2 flame. |
|
Conductor | 50 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more conductors, twisted pairs, or groups of twisted conductors. The conductors may be laid parallel or twisted together to form a flat, oval, or round cable construction. Barrier layer, tapes and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly. |
|
Covering | Optional |
|
Shield | Optional |
|
Jacket | Extruded TPE. |
| Diameter of cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Special - External Wiring with FT2 Flame rating. |
|