APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22511 Issued:2024-05-29
Revised:New
Style 22511 Multiple-conductor cable using non-integral jacket

Rating105 deg C, 300 Vac, FT2 flame.
Conductor50 AWG - 2000 kcmil, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more conductors, twisted pairs, or groups of twisted conductors. The conductors may be laid parallel or twisted together to form a flat, oval, or round cable construction. Barrier layer, tapes and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional
ShieldOptional
JacketExtruded TPE.
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.000 inch110 mils88 mils
4.001 inch and larger140 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial - External Wiring with FT2 Flame rating.

UL and the UL Logo are trademarks of UL LLC © 2025