APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 22547 Issued:2024-10-01
Revised:2024-10-02
Style 22547 Multiple-conductor cable using non-integral jacket.

Rating90 deg C, 1000 Vac, Horizontal Flame.
Conductor40 AWG min. solid or stranded round.
InsulationLabeled or complies with manufacturer's Singles AWM Procedure rated 90 deg C min and a voltage rating equaling or exceeding the rating of the cable.
AssemblyTwo or more singles or groups of twisted singles twisted together. Lay not specified. Barrier layer, shield, braid and/or fillers optional.
JacketExtruded TPU -
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.500 inch110 mils88 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.