APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2341 Issued:1962-07-10
Revised:2011-12-02
Style 2341 Multiple-conductor cable using non-integral jacket

Rating105 deg C, 300 Vac, Horizontal flame.
ConductorTwo No. 22 AWG, solid or 7/30 stranded, bare or tinned copper.
InsulationPVC, 15 mils min average, 13 mils minimum at any point.
AssemblyTwo conductors laid parallel, or twisted.
ShieldA black conductive thermoplastic (PVC) material, nominal 10 mils thick (8.5 mils min.) shall be applied over both conductors, in conjunction with a parallel applied drain wire solid or 7/30 stranded, bare or tinned copper located between the insulated conductors and the conductive thermoplastic.
JacketPVC, 15 mils min average, 12 mils minimum at any point, color other then black.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseIn electronic equipment at a maximum operating temperature of 105 deg C.