Rating | 60 deg C, 30 Vac, Cable flame. |
|
Insulated Conductor | 40 AWG minimum. Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two or more insulated conductors, twisted pairs or groups of twisted insulated conductors twisted together. The insulated conductors or groups of insulated conductors may be laid parallel forming a flat, oval or round cable. The lay of the insulated conductors is not specified. Barrier layers, binders over groups of conductors and/or the complete conductor assembly and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional, extruded PVC, 6 mils minimum thickness at any point, over one or more groups of insulated conductors. |
|
Shield | Optional, over one or more groups of insulated conductors and/or the complete conductor assembly. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket* | Minimum average thickness | Minimum thickness at any point |
| 0.425 inch or less | 30 mils | 24 mils |
| 0.426-0.700 inch | 45 mils | 36 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.000-1.500 inch | 80 mils | 64 mils |
| 1.501-2.500 inch | 110 mils | 88 mils |
| 2.501 inch and larger | 140 mils | 112 mils |
| * - Major diameter if cable is flat or oval. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring in Class 2 circuits of computers and electronic equipment. |
|