APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2410 Issued:1965-05-03
Revised:2012-04-03
Style 2410 Pararell cable with extruded integral insulation and jacket.

Rating80 deg C, voltage not specified, FT-2 flame.
Conductor12 AWG consisting of 65 of 30 AWG strands.
Integral Insulation and JacketExtruded PVC. Similar to Type SPT-3 except with a nominal 60 mils and the following nominal dimensions: Wall thickness - 60 mils, Web thickenss - 110 mils.
AssemblyTwo conductor, same as type SPT-3
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseLow voltage outdoor application in lighting fixtures. Polarity identification may be omitted.