Rating | 90 deg C, 600 Vac, Cable flame, Oil Resistant 60 deg C , Moisture Resistant 60 deg C |
|
Insulation | Labeled AWM or singles complying with this manufacturer's AWM Procedure. |
|
Assembly | Two or more conductors. Two conductor cable may be flat or twisted. If more than one group is used, groups shall be twisted together. (The length of lay of the twisted conductors or groups is not specified). Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap, serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. |
|
Shield | Optional. |
|
Jacket | Extruded PVC, 110 mils min average, 88 mils minimum at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External and internal wiring. |
|